§ 15-1-52. CONSTRUCTION REQUIREMENTS FOR SOLE SOURCE PURCHASER.  


Latest version.
  • A public water system that purchases or obtains water from the City as a sole source through a connection made after January 12, 2004 shall, before using the connection:

    (1)

    install, test, and maintain a backflow prevention assembly at each service connection to the City's public water system;

    (2)

    install one or more gravity overflows at a receiving vessel or reservoir with a minimum capacity equal to or greater than the maximum possible fill rate at 60 pounds per square inch at the base of the vessel or reservoir; or

    (3)

    install an air gap external to a tank or receiving vessel at a service connection.

Source: Ord. 040108-3.