A person shall not discharge or allow the discharge to the POTW of wastewater containing the following individually identified specific pollutants in concentrations, solution, or suspension that exceed the following limits:
Pollutant Milligrams per Liter (1) Arsenic, Total (T) 0.2 (2) Cadmium (T) 0.4 (3) Chromium (T) 2.4 (4) Copper (T) 1.1 (5) Cyanide (T) 1.0 (6) Fluoride (T) 65.0 (7) Lead (T) 0.4 (8) Manganese (T) 6.1 (9) Mercury (T) 0.002 (10) Molybdenum (T) 1.1 (11) Nickel (T) 1.6 (12) Selenium (T) 1.8 (13) Silver (T) 1.0 (14) Zinc (T) 2.3