§ 25-12-114. LOCAL AMENDMENTS TO THE ELECTRICAL CODE - TECHNICAL.


Latest version.
  • The following provisions are local amendments to the 2017 Electrical Code. Each provision of this section is a substitute for any identically numbered provision of the 2017 Electrical Code deleted by Section 25-12-111(B) ( National Electrical Code ) or is an addition to the 2017 Electrical Code:

    110.12 Mechanical Execution of Work. Neat and workmanlike. All electrical work shall be installed in a neat and workmanlike manner. In the Electrical Code, workmanlike manner means, but is not limited to, the following:

    1.

    work that is skillfully installed consistent with the Electrical Code's requirements;

    2.

    equipment, raceways, and cables are installed parallel or perpendicular to the building or structure's structural members;

    3.

    when raceways or cables are grouped, the raceways and cables remain straight, parallel, or perpendicular to the building or structure's structural members;

    4.

    each cable is cut to a length that prevents sagging or looping, except when flexibility requires moderate sagging; and

    5.

    each box, cabinet, enclosure, and device is installed level, parallel, or perpendicular to the building or structure's structural members.

    200.6 Means of Identifying Grounded Conductors.

    (A)

    Sizes smaller than 8 AWG. An insulated grounded conductor smaller than 8 AWG shall be identified by one of the following means:

    1.

    a continuous white outer finish;

    2.

    a continuous gray outer finish;

    3.

    three continuous white strips along the conductor's entire length on other than green insulation;

    4.

    a wire that has an outer covering finished to show white or gray color but have colored tracer threads in the braid that identify the source of the manufacturer complies;

    5.

    the grounded conductor of a mineral-insulated, metal-sheathed cable shall be identified at the time of installation by a distinctive marking at its terminations;

    6.

    a single-conductor, sunlight-resistant, outdoor-rated cable used as a grounded conductor in photovoltaic power systems, as authorized in Section 690.31, shall be identified at the time of installation by distinctive white marking at all terminations;

    7.

    a fixture wire shall comply with the requirements for grounded conductor identification required in Section 402.8; and

    8.

    for an aerial cable, the identification shall comply with the means described above or by means of a ridge located on the exterior of the cable so as to identify it.

    (B)

    Sizes 8 AWG and larger. An insulated grounded conductor of 8 AWG or larger shall be identified by one of the following means:

    1.

    a continuous white outer finish;

    2.

    a continuous gray outer finish;

    3.

    three continuous white or gray strips along the conductors entire length on other than green insulation; or

    4.

    at the time of installation, by a distinctive white or gray marking at its termination, which shall encircle the conductor or insulation.

    225.32 Location. Subsection 230.70(A)(1) of the Electrical Code provides disconnect requirements for outside feeder and branch circuits.

    Exception. For a tower or pole used as a lighting standard, the disconnecting means may be located elsewhere on the premises.

    Exception. For a pole or other similar structure used only for support of signs installed consistent with Article 600, the disconnecting means may be located elsewhere on the premises.

    230.54(H) Identification of conductors at weather head. All service entrance conductors shall be identified within 12 inches of a rain-tight service head.

    230.70(A)(1) Readily accessible location. The service disconnecting means shall be installed at a readily accessible location outside of the building or structure.

    Exception: Commercial Buildings and Structures. When the customer is the only customer served by the utility transformer, the service disconnecting means shall be located on the first floor of the building or structure nearest the point of entrance of the service conductors. The disconnecting means shall be accessible from an exterior entrance and may not exceed 25 feet inside the building or structure.

    250.68(A)(1) Concrete encased electrode accessibility. Concrete encased electrode accessibility for the electric utility district (EUD) locations (having no wall rough-in inspection) shall require a grounding inspection port for termination of the grounding electrode conductor. The inspection port enclosure shall be accessible from the exterior wall of the building or structure and a minimum size of 4 inches by 4 inches by 2½ inches and identified as "ground port" on the cover plate or door of the port.

    250.119 Identification of equipment grounding conductors.

    (A)

    Conductors sizes 8 AWG and larger. A conductor size 8 AWG or larger may be marked at each accessible point. An equipment grounding conductor size 8 AWG or larger shall comply with Section 250.119(A)(1) and (A)(2).

    (1)

    An insulated or covered conductor size 8 AWG or larger may, at the time of installation, be permanently identified as an equipment grounding conductor at each end and at every point where the conductor is accessible.

    Exception. A conductor size 8 AWG or larger is not required to be marked in conduit bodies that contain no splices or unused hubs.

    (2)

    Identification shall encircle the conductor and shall be accomplished by one of the following:

    a.

    stripping the insulation or covering from the entire exposed length;

    b.

    coloring the insulation or covering green at the termination; or

    c.

    marking the insulation or covering with green tape or green adhesive labels at the termination.

    300.3(C)(1) Conductors of different systems. Feeders and branch circuits of solidly grounded wye electric systems that operate at less than 150 volts to the ground may not occupy the same wireway, raceway, junction box, pull box, outlet box, or enclosure with feeders or branch circuits of solidly grounded wye electric systems that operate at more than 150 volts to the ground.

    300.11(E) Suspended ceilings. A cable, raceway, or box may not be supported or attached to the framing members (grid) of a suspended ceiling system.

    310.106(A)(1) Minimum size of conductors. No. 14 AWG copper is allowed for residential use only. Aluminum or copper-clad aluminum may not be smaller than No. 8 AWG.

    Exception. Unless allowed by another provision of the Electrical Code.

    310.110(C)(1) Conductor Identification.

    (A)

    Color coding of conductors shall be consistent throughout each system and identified as follows:

    (1)

    Single phase 120/240 volt wiring system.

    (A)   (B)   (N)

    RED—BLACK—WHITE

    (2)

    Three phase four wire 120/208 volt wiring system.

    (A)   (B)   (C)   (N)

    RED—BLACK—BLUE—WHITE

    (3)

    Three phase three, and four wire 120/240 volt delta wiring systems.

    (A)   (B)   (C)   (N)

    RED—ORANGE—BLACK—WHITE

    (4)

    277/480 wye or 480 volt delta wiring systems.

    (A)   (B)   (C)   (N)

    BROWN—YELLOW—PURPLE—GRAY

    The identification requirements for equipment grounding conductors are established in Section 250.119(A) of the Electrical Code.

    The identification requirements for grounded conductors are established in Subsections 200.6(A) and (B) of the Electrical Code.

    330.12(3) Uses not permitted. Type MC cable may not be used as a service or feeder entering a surface mounted electrical cabinet or panelboard for MC cable smaller than No. 8 AWG.

    330.30 Securing and supporting.

    (A)

    General. Type MC cable shall be installed in a workmanlike manner and consistent with the Electrical Code. When installed in a surface mounted panel, the type MC cable shall be No. 8 AWG or larger.

    (B)

    Securing. Type MC cable shall be supported and secured at intervals that do not exceed 6 feet (1.83 m) when concealed, 3 feet (0.915 m) when exposed, and within 12 inches (305 mm) of a connection to every panelboard or terminal/box.

    (C)

    Supporting. No more than three cables may be bundled for each support ring. If more than three cables are required in an exposed location, the cable shall be racked together and uniformly spaced in parallel runs supported by a steel channel. The steel channel shall be designed and listed for the application. Cables shall be fastened to the channel with metal cable clamps designed for the channel used.

    334.10 Uses permitted. Type NM, Type NMC, and Type NMS cables may be used for systems that operate at a maximum of 150 volts to ground in:

    (1)

    one- and two-family dwellings and their attached or detached garages, and their accessory buildings; or

    (2)

    except as prohibited in Section 334.12, multifamily dwellings and their associated uses that are Types III, IV, and V construction; or

    (3)

    dwelling units, sleeping units, guest rooms, and guest suites in Group R, as that term is used in the Building Code, facilities of Types III, IV, and V construction.

    Exception: In an existing structure that was legally constructed with non-metallic sheathed cable, the non-metallic sheathed cable may remain as the wiring method for the existing structure when:

    a.

    it is a remodel of a Type III, IV, or V construction;

    b.

    it is two stories or less in height;

    c.

    it is supplied by a 120/240 volt single-phase electrical service; and

    d.

    it is not used for areas or equipment regulated by Chapters 5, 6, and 7 of the Electrical Code.

    680.13(1) Emergency switch for swimming pools. A clearly labeled emergency shutoff switch shall be installed to disconnect all ungrounded conductors for swimming pool equipment and underwater lighting systems. The switch shall be installed in a place that is readily accessible, within sight, and not less than five feet from the water's edge. The sign for the shut-off switch shall be in red with letters capable of being read from a distance of 50 feet; shall be made of plastic, metal, or other durable material; and shall read "Emergency Shut Off". The switch shall be red and of the mushroom type, push to de-energize.

    Exception: One- and two-family dwellings.

    680.23(A)(4) Voltage limitation. An underwater luminaire or other underwater lighting system that is permanently installed in a swimming pool, spa, hot tub, fountain, or similar installation shall be listed as a lighting system of 16 volts or less.

    680.41 Emergency shut-off for spas and hot tubs.

    (A)

    A clearly labeled emergency shutoff switch shall be installed to disconnect all ungrounded conductors for spa or hot tub equipment and underwater lighting systems. The switch shall be installed in a place that is readily accessible, within sight, and not less than five feet from the water's edge.

    (B)

    The sign for the shut-off switch shall be in red with letters capable of being read from a distance of 50 feet; shall be made of plastic, metal, or other durable material; and shall read "Emergency Shut Off".

    (C)

    The switch shall be red and of the mushroom type, push to de-energize.

    Exception: One- and two-family dwellings.

    700.10(A)(3) Emergency systems shall be permanently identified red in color.

Source: Ord. No. 20170928-094 , Pt. 1, 1-1-18.

Editor's note

Part 2 of Ord. No. 20170928-094 states, "This ordinance takes effect on January 1, 2018."