§ 6-1-14. REFRIGERATION CHILLERS.  


Latest version.
  • A person who owns or operates a centrifugal chiller that uses a refrigerant shall:

    (1)

    install leak monitoring equipment in the mechanical equipment room;

    (2)

    check the leak monitoring equipment at least once each month;

    (3)

    if the leak monitoring equipment registers a leak of 10.0 parts per million or more, repair the chiller within 30 days; and

    (4)

    if the chiller uses refrigerant R-11 and is not operated continuously, install and maintain a positive pressure device or a high efficiency purge device.

Source: 1992 Code Section 4-3-13; Ord. 031023-10; Ord. 031211-11.