§ 6-1-14. REFRIGERATION CHILLERS.
A person who owns or operates a centrifugal chiller that uses a refrigerant shall:
(1)
install leak monitoring equipment in the mechanical equipment room;
(2)
check the leak monitoring equipment at least once each month;
(3)
if the leak monitoring equipment registers a leak of 10.0 parts per million or more, repair the chiller within 30 days; and
(4)
if the chiller uses refrigerant R-11 and is not operated continuously, install and maintain a positive pressure device or a high efficiency purge device.