§ 3.2.10. Fire Protection Equipment Inspection Schedule  


Latest version.
  • Type of System Test Frequency Qualified Personnel
    Fire Alarm and Detection System Annually, Semiannually, quarterly, and monthly in accordance with NFPA 72 State Licensed Fire Alarm Company, except monthly and quarterly tests by building engineering staff when approved by AFD
    Magnetic Locks and Stairway Door Locks Annually (quarterly function test by building engineering staff for high rise buildings) *Building Engineering Staff
    Fire Pump Annually (quarterly function test by building engineering staff for high rise buildings) State Licensed Automatic Sprinkler Company
    Standpipes 5 year, Annually, quarterly and monthly in accordance with NFPA 25 State Licensed Automatic Sprinkler Company, or Licensed Master Plumber (for Independent Standpipe Systems only). Quarterly and monthly tests may be by building staff when approved by AFD.
    Automatic Sprinklers 5 year, Annually, quarterly and monthly in accordance with NFPA 25. State Licensed Sprinkler Company. Quarterly and monthly tests may be by building staff when approved by AFD.
    Shaft Pressure Annually (quarterly function test by building engineering staff for high rise buildings) Special Inspection Agency or Service
    Emergency Generators Annually (quarterly function test by building engineering staff for high rise buildings) Licensed Master Electrician or authorized Generator Company Service Representative
    Elevators Annually (quarterly function test by building engineering staff for high rise buildings) Elevator Company Service Representative (or as approved by Building Official)
    Tempered Windows/Smoke Removal Annually (quarterly function test by building engineering staff for high rise buildings and atrium systems) Building Engineering Staff (Tempered Windows Only), or Special Inspection Agency or Service
    Sequence Test Annually Austin Fire Dept.
    Foam Systems Annually/5 year Licensed Fire Protection System Co.
    Fire Escape 5 year (annual function test by building engineer) Licensed Professional Engineer
    Halon, CO2 or Halon Alternative Agents Annually Licensed Fire Protection System Company
    Range Hoods Semi-annually Licensed Fire Protection System Company
    Dry Chemical Semi-annually Licensed Fire Protection Systems Company
    Evacuation Plans Annually Austin Fire Dept.
    Fire Hydrants Annually W& WW Approved Organization or Contractor
    * Building engineering staff is acceptable provided a responsible person is designated who has specialized knowledge of the system being inspected and any related building systems which may be present.