§ 3.2.6. Night Inspections
A.
This type of inspection is performed where the occupant load is near capacity during the evening hours, (i.e., nightclubs, drinking and dining establishments), other places of assembly (theaters, auditoriums, etc.) or buildings or facilities which can only be checked at night (i.e., offices with irregular hours, etc.).
B.
The general procedures used during the inspection of premises for night inspections may include those procedures outlined in Section 3.2.3 "General Fire Safety Inspections", above, but primarily involve the following:
1.
Verify the exiting system is unlocked, unobstructed exit signs illuminated and aisles leading to exits have required unobstructed width.
2.
Verify no more people are inside the building than what is indicated on occupant load card(s).
3.
Verify the fire protection systems are operational and maintained according to the Fire Code.